工(gong)業冷水機安裝要求:

1.電源

(1)、冷(leng)水機(ji)組(zu)電(dian)(dian)源(yuan)采用三相四線(xian)、電(dian)(dian)源(yuan)線(xian)(R、S、T)接(jie)電(dian)(dian)源(yuan)火線(xian),(N)接(jie)零線(xian),(G)接(jie)地線(xian)。

(2)、機組用主(zhu)電(dian)源線(xian)線(xian)電(dian)控(kong)箱(xiang)上(shang)的穿孔連(lian)接(jie)在箱(xiang)內接(jie)柱(zhu)上(shang),保證連(lian)接(jie)緊固。 (3)、機組配(pei)電(dian)要求:主(zhu)電(dian)源電(dian)壓(ya):額定電(dian)壓(ya)±10%以內。

(4)、主電源電壓(ya)波(bo)動超過(guo)規定范圍(wei)時,不準(zhun)起(qi)動冷水機、否(fou)則視作(zuo)(zuo)操(cao)作(zuo)(zuo)不當,由此引起(qi)的損壞不在本(ben)公司(si)保養范圍(wei)之內。

(5)、水(shui)(shui)(shui)系統之水(shui)(shui)(shui)流開關(guan)、水(shui)(shui)(shui)泵、冷卻水(shui)(shui)(shui)塔(ta)電(dian)機(ji)等聯鎖電(dian)路必(bi)要時(shi)可正確(que)連接在機(ji)組控制電(dian)路中。

(6)、冷(leng)水(shui)機組設(she)有(you)電(dian)(dian)(dian)流過載保(bao)護、壓縮機排氣端之(zhi)高低壓保(bao)護,馬達線圈過熱保(bao)護、防(fang)冰保(bao)護,冷(leng)卻水(shui)之(zhi)水(shui)流連(lian)鎖保(bao)護等多種措施,控制電(dian)(dian)(dian)路(lu)先進。本公(gong)司冷(leng)水(shui)機組的控制電(dian)(dian)(dian)路(lu)已在(zai)工廠里安裝調試完成。切(qie)勿擅自(zi)改(gai)動、如需改(gai)動請與本公(gong)司聯絡。

2.安裝 

為(wei)確保空調系統的(de)安全及正常運(yun)行,防止不適當的(de)水配管路施工(gong)造成的(de)冷(leng)水機故障,安裝本機組時應注意(yi)下列(lie)事項:

(1)、吊運安裝冷水(shui)機時注(zhu)意不要損壞機組(zu),合理布局冷水(shui)機周圍空間(jian),以方便維修保(bao)養冷水(shui)機。

(2)、按照(zhao)國(guo)家標準對配管系統(tong)設計及施工安(an)裝(zhuang)的要求,合理(li)設計和(he)安(an)裝(zhuang)凍水(shui)(shui)(shui)及冷卻水(shui)(shui)(shui)系統(tong),以充分發(fa)揮冷水(shui)(shui)(shui)機性能。

(3)、機(ji)組應水平(ping)放置,及安裝在通風位置。

(4)、根(gen)據(ju)機組制冷能力(li)選用(yong)匹配的冷卻塔(ta)。

(5)、機組配管(guan)(guan)請參照本(ben)公司建議(yi)之配管(guan)(guan)方(fang)法安裝(zhuang)施工。

(6)、水(shui)源及(ji)散熱水(shui)塔(ta)周圍環境惡劣時,冷凍(dong)水(shui)和冷卻水(shui)回路必(bi)須安裝(zhuang)(zhuang)Y型過濾器及(ji)定時清理,封閉冷凍(dong)水(shui)系統(tong)最高處(chu)必(bi)須安裝(zhuang)(zhuang)自動排(pai)氣閥、系統(tong)最低處(chu)安裝(zhuang)(zhuang)排(pai)水(shui)接頭,以系統(tong)排(pai)水(shui)用。

(7)、冷(leng)凍水管路系(xi)統通過試漏(lou)后,包保溫(wen)層(ceng),避免(mian)冷(leng)量散(san)失及管路滴水。